انجمن آب و فاضلاب ایرانعلوم و مهندسی آب و فاضلاب2588-39412320170923Studying the Performance of Different Approaches for PRVs Setting and improving reliability in Water Distribution Networksبررسی و مقایسه کارایی رویکردهای مختلف تنظیم شیرهای فشارشکن در بهبود قابلیت اطمینان شبکههای توزیع آب4136059110.22112/jwwse.2018.89166.1026FAمحمدامین غیبیفارغ التحصیل دانشگاه تهرانمیلاد لطیفیدانشجوی دکتری دانشکده مهندسی عمران، پردیس دانشکدههای فنی، دانشگاه تهرانسید تقی امید نایینیدانشگاه تهران- دانشکده فنی- گروه عمرانJournal Article20170729High pressure in water distribution networks leads to various problems such as increased leakage, bursts and unexpected consumptions. Hence, pressure management plans are implemented using pressure reducing valves (PRVs), tanks and pump stations. In this study, PRVs are applied for pressure management in three different approaches; fixed outlet, time modulation and flow modulation. In fixed outlet PRVs, a steady set pressure is considered for each PRV during the day. A simulation-optimization model is developed to find the optimal set pressures for all PRVs. In time modulation approach, PRVs are able to apply different pressure settings at different hours of the day which results the better control of the hourly pressure fluctuations in the water network. In this approach, optimization of set pressures is carried out. In flow modulation PRVs, the set pressure is regulated according to the average pressure in the network. In addition, in this study a new reliability index is introduced considering the average pressure and hourly pressure fluctuations and their effects on consumer’s satisfaction. This index is considered as an optimization objective function. Finally, comparing the performance of the above approaches shows that flow modulation, time modulation and fixed outlet approach are the most reliable, respectively.بالا بودن فشار در شبکههای توزیع آب موجب بروز مشکلات متعددی مانند افزایش نشت، حوادث و مصرف ناخواسته میشود. بدین منظور برنامههای مدیریت فشار با بکارگیری شیرهای فشارشکن، مخازن و پمپها اجرا میشوند. در این تحقیق از شیرهای فشارشکن با سه رویکرد فشار خروجی ثابت، نوسان زمانی و نوسان دبی برای مدیریت فشار در شبکه توزیع آب استفاده شده است. در شیرهای با خروجی ثابت، یک فشار تنظیمی یکسان در تمام ساعات بر روی جریان اعمال می شود. یک مدل شبیهساز و بهینهساز برای یافتن تنظیمات بهینه این شیرها توسعه داده شده است. شیرهای نوسان زمانی قادر هستند در ساعات مختلف شبانهروز، فشار تنظیمی متغیری را اعمال نمایند. بدینترتیب میتوان نوسانات ساعتی فشار در شبکه را بهتر کنترل نمود. در این مورد هم بهینهسازی تنظیمات شیرها انجام شده است. در شیرهای نوسان دبی با توجه به فشار متوسط شبکه مقدار فشار خروجی تنظیم میگردد. به علاوه، در این پژوهش شاخص قابلیت اطمینان جدیدی بر پایه ی رضایت مشترکین و لحاظ نمودن اثر نوسانات و متوسط فشار، معرفی و به عنوان تابع هدف بهینهسازی بکارگرفته شده است. در نهایت و با مقایسه عملکرد رویکردهای مذکور ملاحظه گردید که بهترتیب رویکردهای نوسان دبی، نوسان زمانی و خروجی ثابت دارای بیشترین اطمینانپذیری هستند.انجمن آب و فاضلاب ایرانعلوم و مهندسی آب و فاضلاب2588-39412320170923Concept of DALY Index and its Calculation in Estimating Disease Burdenمفهوم و محاسبهی شاخص DALYs در برآورد بار بیماریها14206059210.22112/jwwse.2018.91896.1035FAکاوه علی نژادرییس گروه اجرای طرح های فاضلاب / شرکت مهندسی آب و فاضلاب کشورJournal Article20170715Simultaneous with the change in the sequence and track of diseases, referred to as the "epidemiological transmission of illnesses", and for the aim of measuring early deaths and disabilities, the use of a common basis seems essential. Since the late 1940s, researchers have identified 'time' as a common criterion for measuring early deaths and disabilities, and based on that, the DALYs have been introduced. This index, which is used in economic assessments and calculation of health expenditures and functions, consists of two factors: "years of life that are lost due to premature death" and "years of life associated with a type of disability with specific intensity and duration ". The World Health Organization has used this index in developing its guidelines for the microbial, chemical and radioactivity quality of drinking water. In this paper, while presenting the basic concepts of DALYs, how it is calculated correctly in an effective cost estimate is presented in the form of an applied example.همزمان با تغییر در ترتیب و توالی بیماریها که از آن به "انتقال اپیدمیولوژیک بیماریها" نام برده میشود و با هدف همسانسازی و سنجش مشترک مرگهای زودرس و ناتوانیها، استفاده از یک مبنای مشترک ضرورت دارد. از اواخر دههی 1940، پژوهشگران "زمان" را به عنوان معیار مشترک سنجش مرگهای زودرس و ناتوانیها تعیین و بر مبنای آن شاخص DALYs را معرفی کردهاند. این شاخص که از آن در ارزیابیهای اقتصادی و محاسبهی هزینهها و عملکردهای بهداشتی استفاده میشود، متشکل از دو عامل "سالهایی از عمر که با مرگ زودرس از بین میرود" و "سالهایی از عمر که همراه با نوعی ناتوانی با شدت و طول مدت خاص سپری میشود"، میباشد. سازمان جهانی بهداشت نیز در تدوین مقادیر رهنمودی خود برای کیفیت میکروبی، شیمیایی، و رادیواکتیویتهی آب آشامیدنی از این شاخص بهره گرفته است. در این مقاله ضمن ارایهی مفاهیم پایه از DALYs، چگونگی محاسبهی صحیح آن در برآورد هزینهی موثر، در قالب یک مثال کاربردی بیان شده است.انجمن آب و فاضلاب ایرانعلوم و مهندسی آب و فاضلاب2588-39412320170923Study on the effective process parameters for degradation of herbicide Bentazone in contaminated water by nano metal oxides of Titanium (IV) and Iron (III) based on natural zeoliteبررسی عوامل موثر فرآیندی در تخریب علف کش بنتازون در آبهای آلوده توسط نانواکسیدهای فلزی تیتانیوم (IV) و آهن (III) بر پایه زئولیت طبیعی21326059310.22112/jwwse.2018.92536.1037FAمهرداد فرهادیاناصفهان ، خیابان هزارجریب ، دانشگاه اصفهان ، دانشکده فنی و مهندسی ، گروه مهندسی شیمیآرش ساکیدانشجوی کارشناسی ارشد دانشکده مهندسی شیمی، نفت و گاز، دانشگاه شیراز، شیراز، ایراننیلا داوریدانش آموخته کارشناسی ارشد گروه مهندسی شیمی، دانشکده فنی مهندسی، دانشگاه اصفهان، اصفهان، ایرانJournal Article20170716In this study, the photocatalyst of TiO2/Fe2O3 based on clinoptilolite natural zeolite was synthesized by co-precipitation method and its function in degradation of Bentazone, as one of the most widely used herbicides in agriculture, was evaluated. The effect of process parameters simultaneously including pollutant concentration (1-40 mg/l), pH (4-10) and hydrogen peroxide concentration (25-100 mg/l) on photocatalytic degradation efficiency of Bentazone was investigated using design of experiments in response surface methodology. Synthesized photocatalyst was characterized by XRD, XRF, FT-IR, FE-SEM and EDX analyses. The results of XRD, FT-IR, and EDX confirmed the presence of TiO2 and Fe2O3 nanoparticles on the surface of clinoptilolite. The FE-SEM results confirmed the deposition of TiO2/Fe2O3 on the surface of clinoptilolite zeolite and also the approximate particle size of TiO2/Fe2O3 was 52 nm. According to XRF results, the synthesized nanoparticles had Fe3+/TiO2 optimal molar ratio of 0.06. The results showed that Bentazone concentration, pH and hydrogen peroxide concentration were the most effective factors on photocatalytic degradation efficiency of Bentazone, respectively. According to the experimental data at optimal conditions (pH, pollutant concentration and hydrogen peroxide concentration are 10, 10 mg/l and 50 mg/l, respectively), degradation efficiency of Bentazone was obtained 97% and the degradation efficiency was 78% at maximum concentration of pollutant (40 mg/l). This study showed that the synthesized photocatalyst has acceptable efficiency for degradation of non-biodegradable pollutant and removal pesticides from contaminated water.در این پژوهش فتوکاتالیست ترکیبی اکسید تیتانیوم و اکسید آهن بر پایه زئولیت طبیعی کلینوپتیلولایت به روش همرسوبی شیمیایی سنتز شد و عملکرد آن در تخریب بنتازون بهعنوان یکی از پرمصرفترین علف کشها در کشاورزی مورد ارزیابی قرار گرفت. اثر همزمان عوامل فرآیندی شامل غلظت آلاینده (mg/l 40-1)، pH محلول (10-4) و غلظت هیدروژن پراکساید (mg/l 100-25) بر بازده تخریب فتوکاتالیستی بنتازون با استفاده از طراحی آزمایشها به روش سطح پاسخ بررسی گردید. مشخصه یابی فتوکاتالیست سنتز شده توسط آنالیزهای XRD، XRF، FT-IR، FE-SEM و EDX انجام گرفت. نتایج XRD، FT-IR و EDX حضور نانو ذرات اکسید تیتانیوم و اکسید آهن را بر سطح زئولیت کلینوپتیلولایت تأیید کردند. نتایج FE-SEM ضمن تأیید لایه نشانی اکسید تیتانیوم و اکسید آهن بر سطح زئولیت کلینوپتیلولایت، سایز تقریبی نانو ذرات را nm 52 نشان داد. مطابق با نتایج XRF، نانو ذرات سنتز شده با نسبت مولی بهینه Fe3+ به TiO2 برابر با 06/0 حاصل شدند. نتایج این پژوهش نشان داد که غلظت محلول بنتازون، pH اولیه محلول و غلظت هیدروژن پراکساید به ترتیب بیشترین اثر را بر بازده تخریب فتوکاتالیستی بنتازون دارند. مطابق با نتایج تجربی در شرایط بهینه (pH اولیه محلول، غلظت آلاینده و غلظت هیدروژن پراکساید به ترتیب برابر با 10، mg/l 10 و mg/l 50) بازده تخریب بنتازون 97% به دست آمد و در حداکثر غلظت آلاینده (mg/l 40) بازده تخریب 78% حاصل شد. این پژوهش نشان داد که فتوکاتالیست سنتز شده بازده قابل قبولی در تخریب آلاینده زیست تخریب ناپذیر و حذف سموم کشاورزی از آبهای آلوده دارد.انجمن آب و فاضلاب ایرانعلوم و مهندسی آب و فاضلاب2588-39412320170923The investigation of using biological and chemical oxidation combination effect on wastewater treatmentتاثیر استفاده از فرآیند ترکیبی اکسیداسیون شیمایی و بیولوژیکی در تصفیه فاضلاب33406059410.22112/jwwse.2018.97395.1044FAداود کاه فروشانرییس مرکز تحقیقات مهندسی محیط زیست، دانشکده مهندسی شیمی، دانشگاه صنعتی سهندعلی برادر خوش فطرتدانشکده مهندسی شیمی، دانشگاه صنعتی سهندرضا ایرانیدانشگاه صنعتی سهند- دانشکده مهندسی شیمیJournal Article20170904Recently, the use of hybrid techniques is taken into consideration in wastewater treatment to achieve a high efficiency and effective removal of contaminants especially for resistant contaminants. In this research, the process of a combination of chemical oxidation by ozone and biological oxidation by aerobic attached growth bioreactor in the different modes for treating of wastewater were studied. At first, the performance of aerobic biological reactor was alone studied. Synthetic wastewater (sodium acetate as carbon source and ammonium chloride as a source of nitrogen) with the initial COD of 300 ppm and the ratio of carbon to nitrogen of 10 was used. The results showed that there is a complete nitrification in bioreactor and COD removal efficiency is 89%. When using ozone oxidation before biotreatment, it was seen that the efficiency of COD removal increased to 94.0% and TSS was achieved to 75 mg/L in output. In the next step, the ozonation was used after biotreatment and it was observed that COD removal efficiency increased to 97.0% and the amount of TSS also decreased to 35 mg/L in output. In the final step, ozonation was used simultaneously before and after biotreatment as pretreatment as well as final treatment. In this mode, the results showed that the efficiency of COD removal in the output of the system increased to 98.3% and the value of TSS was declined to 20 mg/L.در حال حاضر استفاده از روش های ترکیبی برای رسیدن به بازده بالا در تصفیه فاضلاب ها و حذف موثر آلاینده ها بخصوص آلاینده های مقاوم مورد توجه قرار گرفته است. در این تحقیق به صورت آزمایشگاهی، فرآیند ترکیبی ازناسیون توسط ازن و اکسیداسیون بیولوژیکی توسط راکتور بیولوژیک چسبیده هوازی در حالتهای مختلف برای تصفیه فاضلاب مورد بررسی قرار گرفت. در ابتدا عملکرد راکتور بیولوژیک رشد چسبیده هوازی به تنهایی مورد بررسی قرار گرفت. فاضلاب سنتزی(استات سدیم به عنوان منبع کربن و از آمونیوم کلراید به عنوان منبع نیتروژن ) با COD اولیه mg/L 300 و نسبت کربن به نیتروژن برابر با 10 مورد استفاده قرار گرفت. نتایج نشان داد که نیتریفیکاسیون در بیوراکتور به طور کامل انجام گرفته و راندمان حذف COD برابر 89٪ می باشد. وقتی از ازن به عنوان پیش تصفیه قبل از بیوراکتور استفاده شد، مشاهده گردید که راندمان حذف COD در خروجی سیستم به 94٪ افزایش یافت و مقدار TSS نیز به mg/L 75 کاهش یافت. در مرحله بعد ازناسیون به عنوان تصفیه نهایی بعد از بیوراکتورانجام گرفت و مشاهده شد که راندمان حذف COD در خروجی سیستم به 97٪ افزایش یافت و مقدار TSS نیز به mg/L 35 کاهش یافت. در مرحله آخر ازناسیون به طور همزمان هم به عنوان پیش تصفیه قبل از بیوراکتور و هم به عنوان تصفیه نهایی بعد از بیوراکتور استفاده شد، مشاهده شد که راندمان حذف COD در خروجی سیستم به 3/98٪ افزایش یافت و مقدار TSS نیز به mg/L 20 کاهش یافت.انجمن آب و فاضلاب ایرانعلوم و مهندسی آب و فاضلاب2588-39412320170923Study of Biofilm forming Bacteria in Urban Drinking water and the inhibitory methodsبررسی باکتری های تولیدکننده ی بیوفیلم در آب شرب شهری و روش های مقابله با آنها41506059510.22112/jwwse.2018.100297.1045FAزهرا صالحی ریحانیگروه زیست شناسی، دانشگاه آزاد اسلامی واحد دزفول، دزفول، خوزستان، ایران.زهرا خوشنودگروه زیست شناسی، دانشکده علوم پایه، دانشگاه آزاد اسلامی واحد دزفول، دزفول، خوزستان، ایران.Journal Article20171007The maintenance of health and quality of drinking water is one of the major priorities in water supply systems. Formation of biofilm in water pipelines, tanks and domestic water purifiers is one of important concerns. Viruses, bacteria and protozoa could easily transport through water currents and among these, some certain bacteria have the ability of attachment to the surfaces and forming the biofilm. Formation and growth of the biofilm could negatively affect the water current, drinking quality and health. Biofilm forming bacteria secrets protecting compounds which protect them from damaging factors and through this process biofilm become resistant to degradation. Some of the biofilm creating bacteria are also have pathogenic capabilities even in humans, which is crucially important in maintenance of the health of drinking water. Due to the importance of knowing the biofilm forming societies in urban drinking water supply, the present paper will introduce the biofilm and its major bacterial agents.حفظ بهداشت و کیفیت آب آشامیدنی یکی از مهمترین اولویت ها در سیستم های آب رسانی به شمار می رود. تشکیل بیوفیلم برروی سطوح لولههای انتقال آب، مخازن و دستگاههای خانگی تصفیه آب، یکی از مشکلات قابل توجه و مهم در این رابطه میباشد. ویروسها، باکتریها و پروتوزوآها به وسیله آب منتقل می گردند و در این میان، برخی باکتری ها توانایی چسبیدن به سطوح و تولید بیوفیلم را دارند، رشد و گسترش بیوفیلم می تواند علاوه بر ایجاد اختلال در فرآیند جریان آب، بر کیفیت آشامیدنی و بهداشتی آن نیز تاثیر منفی داشته باشد. باکتری های تشکیل دهنده ی بیوفیلم به کمک ترشح ترکیبات محافظتی از خود در برابر عوامل آسیب رسان محافظت می کنند و بدین ترتیب بیوفیلم در برابر تخریب مقاوم می شود. برخی باکتری هایی که قابلیت تولید بیوفیلم دارند، توانایی بیماری زایی در انسان را نیز دارند که این موضوع در حفظ کیفیت و بهداشت آب آشامیدنی اهمیت بالایی دارد. به دلیل اهمیت شناخت جوامع تشکیل دهنده ی بیوفیلم در سیستم های آب شرب شهری، مقاله ی حاضر به معرفی بیوفیلم و مهمترین باکتری های تشکیل دهنده ی آن می پردازد.انجمن آب و فاضلاب ایرانعلوم و مهندسی آب و فاضلاب2588-39412320170923A Survey of Physical, Chemical and Microbial Quality of Drinking Water in Ahvaz Compared to the Drinking Water Standards in Year 2016-2017بررسی کیفیت فیزیکی، شیمیایی و میکروبی آب آشامیدنی شهر اهواز و مقایسه آن با استاندردهای آب شرب در سال 139551606059610.22112/jwwse.2018.101606.1046FAفردوس کریمیکارشناس ارشد مهندسی عمران، مدیر عامل و رئیس هیئت مدیره شرکت آب و فاضلاب اهواز ، اهواز، ایران.نغمه عروجیدانشجو دکترا مهندسی محیط زیستافشین تکدستاندانشیار، مرکز تحقیقات فناوری های زیست محیطی، دانشگاه علوم پزشکی جندی شاپور اهواز، اهواز، ایران.0000-0002-0419-1698Journal Article20171019The physical, chemical and microbial properties of water are the criteria to consider it as drinking water quality. Unfavorable changes in such parameters may threat consumers' health. The aim of this study is to give a clear view of physical , chemical and microbial quality of distribution network drinking water in Ahvaz and compare with national and WHO standards. This study was a cross- sectional survey based on 48-week sampling program in No.1 , 2,3,4and 5 Ahwaz water treatment plants were conducted and six points of water distribution networks.Water of analyses were done according to standard methods. 9 tubeof fermentation method was used to determine fecal and total coliform bacteria. The mean values of measured parameters were as follow: electrical conductivity 2282.5 μs/cm, turbidity 2.3 NTU, pH 7.8, alkalinity 144.8 and hardness 535.5 mg/L as CaCO3, calcium 137.2, magnesium 46.3 , chloride 473.2, sodium 311.2, residual chlorine 1, TDS 1382.7, fluoride 0.53, nitrate 6.7 and sulphate 370.2 mg/L. Total coliform (0), fecal coliform (0) MPN/100 ml. Quality of water from Drinking Water in Ahvaz was not problematical from health point of view. Except EC, hardness , sodium and sulphate all cited results met the national and WHO standards.ویژگی های فیزیکی ، شیمیایی و میکروبی آب آشامیدنی مبنای قضاوت قابل شرب بودن آن است. تغییرات نامطلوب در این پارامترها می تواند سلامت مصرف کنندگان را تهدید کند. لذا هدف از این مطالعه بررسی کیفیت فیزیکی، شیمیایی و میکروبی آب شرب شهر اهواز و مقایسه آن با استانداردهای ملی و سازمان بهداشت جهانی (WHO) می باشد. در این مطالعه که از نوع توصیفی –مقطعی بوده، نمونه برداری در مدت زمان 48 هفته (سال 95) از تصفیه خانه های شماره 1، 2، 3، 4 و 5 شهر اهواز و 6 نقطه در شبکه توزیع آب انجام گرفت. آنالیزهای آب بر اساس روش های مندرج در استاندارد متد صورت گرفت. آزمایشات میکروبی کلیفرم کل و کلیفرم مدفوعی با روش تخمیر نه لوله ای انجام گرفت. میانگین پارامترهای اندازه گیری شده شبکه توزیع آب به ترتیب هدایت الکتریکی2282.5 میکروزیمنس بر سانتی متر، کدورتNTU 2.3، pH 7.8، قلیائیت 144.8 و سختی کل 535.5 میلی گرم بر لیتر بر حسب کربنات کلسیم، کلسیم 137.2، منیزیم 46.3، کلراید 473.2، سدیم 311.2، کلر باقیمانده 1، کل جامدات محلول 1382.7، فلوراید 0.53، نیترات 6.7 و سولفات 370.2 میلی گرم بر لیتر، کلیفرم کل(0)، کلیفرم مدفوعی ) MPN/100mL0( بود. کیفیت بهداشتی آب آشامیدنی شهر اهواز مشکل آفرین نیست. به جزEC ، سختی ، سدیم و کلراید کلیه پارامترها استانداردهای ملی(1053) و WHO آب آشامیدنی را برآورده می نمایند.انجمن آب و فاضلاب ایرانعلوم و مهندسی آب و فاضلاب2588-39412320170923The effect of Interaction between Qanat and Water Distribution in Naser-Khosro Streetتأثیر متقابل قنات و شبکه آب شهری در محدوده خیابان ناصرخسرو تهران616560597FAJournal Article20180418In this paper which is written as an experience acquired from one of the experts in water and wastewater industry, interaction between qanats and municipal water network has been investigated. The recorded experience is about problems seen in Naser-Khosrow street in Tehran during year 1997. After representing the experience and reviewing the case, major difficulties of current qanats located in urban areas together with suggestions to reduce occurrence or effects of this problem is presented. This article can be useful for experts and authorities in urban and rural water and wastewater companies, regional water companies and also consulting engineers and contractors.در این مقاله که به شکل تجربهای کسب شده از یکی از خبرگان صنعت آب و فاضلاب نگاشته شده است تأثیر متقابل قنوات و شبکه آب شهری مورد بررسی قرار گرفته است. تجربه ثبت شده مربوط به مشکلات مشاهده شده در محدوده خیابان ناصرخسروی تهران در سال 1376 میباشد. پس از بیان تجربه و واکاوی آن، عمده مشکلات قناتهای موجود در بافت شهری کشور بههمراه توصیههایی برای کاهش وقوع یا تأثیرگذاری این مشکلات ارائه شده است. این مقاله میتواند برای متخصصین و مسئولین در شرکتهای آب و فاضلاب شهری و روستایی، شرکتهای آب منطقهای و نیز مهندسین مشاور و پیمانکاری مفید باشد.<br />