<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE ArticleSet PUBLIC "-//NLM//DTD PubMed 2.7//EN" "https://dtd.nlm.nih.gov/ncbi/pubmed/in/PubMed.dtd">
<ArticleSet>
<Article>
<Journal>
				<PublisherName>انجمن آب و فاضلاب ایران</PublisherName>
				<JournalTitle>علوم و مهندسی آب و فاضلاب</JournalTitle>
				<Issn>2588-3941</Issn>
				<Volume>2</Volume>
				<Issue>2</Issue>
				<PubDate PubStatus="epublish">
					<Year>2017</Year>
					<Month>06</Month>
					<Day>22</Day>
				</PubDate>
			</Journal>
<ArticleTitle>Controlling the Negative Pressure Caused by Water Hammer in Water Conveyance Pipe Lines Using Hydropneumatics Tank and Air Valves (A Case Study of Mehran City, Ilam Province)</ArticleTitle>
<VernacularTitle>کنترل فشار‌های منفی ناشی از ضربه قوچ در خطوط انتقال آب با ترکیب تانک ضربه گیر و شیر هوا (مطالعه موردی: شهرستان مهران، استان ایلام)</VernacularTitle>
			<FirstPage>34</FirstPage>
			<LastPage>40</LastPage>
			<ELocationID EIdType="pii">58405</ELocationID>
			
<ELocationID EIdType="doi">10.22112/jwwse.2018.88848.1014</ELocationID>
			
			<Language>FA</Language>
<AuthorList>
<Author>
					<FirstName>اسرین</FirstName>
					<LastName>بهرامی</LastName>
<Affiliation>گروه مهندسی آب، دانشکده کشاورزی، دانشگاه ایلام،ایلام،ایران</Affiliation>

</Author>
<Author>
					<FirstName>جعفر</FirstName>
					<LastName>مامی زاده</LastName>
<Affiliation>گروه مهندسی آب، دانشکده کشاورزی، دانشگاه ایلام، ایلام، ایران</Affiliation>

</Author>
<Author>
					<FirstName>علیرضا</FirstName>
					<LastName>حسینی</LastName>
<Affiliation>گروه مهندسی آب، دانشکده کشاورزی، دانشگاه ایلام، ایلام، ایران</Affiliation>

</Author>
<Author>
					<FirstName>حمیدرضا</FirstName>
					<LastName>لطفی زاده</LastName>
<Affiliation>گروه مهندسی عمران، دانشگاه آزاد اسلامی واحد ایلام</Affiliation>

</Author>
</AuthorList>
				<PublicationType>Journal Article</PublicationType>
			<History>
				<PubDate PubStatus="received">
					<Year>2017</Year>
					<Month>06</Month>
					<Day>09</Day>
				</PubDate>
			</History>
		<Abstract>Whenever and for any reason the velocity of the fluid ceases in the transfer line or water distribution networks, pressure waves will form in the pipe lines, which can produce a pressure several times more than a pressure pump’s output and lead to a great deal of tension on network’s components, which in turn will cause the water hammer phenomenon. Today, in every water transfer project, a detailed study on the water hammer phenomenon is essential, so that with a full recognition of this process’s adverse effects, the adequate measures would be taken to deal with it.This study uses Water Hammer V8i software to analyze the water hammer of Mehran city’s border terminal water conveyance pipe. The study was executed in 3 phases of simulation with protective equipment, without the protective equipment and with consultant’s recommended equipment. The results indicate that in the phase without the protective equipment, a great deal of negative pressure builds up along the water conveyance pipe line that needs to be controlled. In the next step, various combinations of Hydropneumatic tank and air valves were suggested. The results of several simulations showed that a 2 square meter Hydropneumatic tank and 3 fifty millimeter air valves will be capable of controlling the negative pressure along the pipe line.</Abstract>
			<OtherAbstract Language="FA">هرگاه در خطوط انتقال یا شبکه‌ها‌ ی توزیع آب ، به هر دلیلی سرعت سیال به طور ناگهانی متوقف شود، امواج فشاری در لوله‌ها به وجود می‌آید که این امواج می‌توانند چندین برابر فشار کار کرد پمپ فشار تولید نموده و موجب به وجود آمدن تنش‌های زیادی در اجزای شبکه و بروز پدیده ضربه قوچ -گردند. امروزه در کلیه طرح های انتقال آب، مطالعه دقیق ضربه قوچ به عنوان یک امر لازم و ضروری می باشد تا با شناخت کامل اثر آن، برای کنترل اثرات سوء این فرآیند تمهیدات مناسب اتخاذ گردد. در این تحقیق از نرم افزار Water Hammer V8i برای تحلیل ضربه قوچ خط انتقال آب پایانه مرزی شهرستان مهران استفاده شد. مطالعه حاضر در سه مرحله به‌صورت شبیه سازی بدون تجهیزات حفاظتی، با تجهیزات حفاظتی و تجهیزات پیشنهادی مشاور صورت گرفت. نتایج تحقیق نشان داد در حالت بدون تجهیزات حفاظتی فشارهای منفی زیادی در طول خط انتقال بوجودآمده و می بایست کنترل گردند. در مرحله بعدی ترکیب‌های مختلف تانک ضربه گیر و شیر هوا پیشنهاد گردید. نتایج شبیه سازی‌های متعدد نشان داد که تانک ضربه گیر 2 متر مکعبی و 3 عدد شیر هوای 50 میلیمتری قادر به کنترل فشار‌های منفی در طول خط می باشد.</OtherAbstract>
		<ObjectList>
			<Object Type="keyword">
			<Param Name="value">ضربه قوچ</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">خط انتقال آب</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">تانک ضربه گیر</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">شیرهوا</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Water Hammer V8i</Param>
			</Object>
		</ObjectList>
<ArchiveCopySource DocType="pdf">https://www.jwwse.ir/article_58405_47e64eab3ac9af3ee72d9e8f4296907f.pdf</ArchiveCopySource>